Guide to connect the Hikvision DSPWA32 alarm panel with the DT42 receiver to send events.
EXTRIUMDT42
To register a Hikvision DSKWA32 alarm panel in the DT42 receiver, the following steps must be carried out:
1. Enter the DT42 receiver and go to the section “Configuration – IP Reception.”
2. On this screen we click on the “Create” button to be able to add a new server.
3. Now we select the type of server “SIADC9” and we continue by clicking on “OK.”
4. Finally we are going to create the server noting the necessary values according to the following screen:
Port: It can be defined by the user and must also be opened in the modem or router, Protocol: TCP.
Encryption Key: it can be any user-defined number like the example shown here.
Now click on “Create”.
5. Now go to section “Alarms and Accounts – Accounts Management”.
6. Now register the account that the alarm panel will communicate with. Now click the “Create” button.
7. A screen appears in which we have to fill in the corresponding data, the most important are “Account Number” and “Name.”
It is recommended that the account number be 4 digits and in the name have our panel well identified. Account numbers must be one per panel.
We finish by clicking on “Create.”
Hikvision Panel DSPWA32
1. We go to the web address of our Hikvision alarm panel and enter the username and password that we have assigned to be able to log in.
2. Once inside the alarm panel configuration, we position ourselves in the part of “Communication parameters – Alarm receiving center.” And we configure it according to the following parameters:
Protocol Type: AMD-CID
Domain Name: Public IP or Domain Name where your monitoring center is located
Port Number: Port defined in your monitoring center
Subscriber code: Account number registered in DT42
Transmission Mode: TCP
We finish by clicking on the save button.
3. To activate the notifications that we want to receive in our monitoring center, select section “Communication parameters – Message notifications” in the “Alarm receiving center” tab and enable each of the desired notifications. Click “Save.”
Example of communication on the DT42 coming from a DSPWA32 alarm panel.